Operation Manual · production-crew audience

ThunderBank

Operation Manual
Lightnin Support · 24/7
470-244-3905
678-472-5682
877-433-0313
Leave voicemail or text if no immediate response. Numbers listed in priority order.
Read alongside: the ThunderBank Emergency Action Plan and the two laminated quick-reference cards (Production Crew + Fire Department). This manual covers normal operation; the EAP covers what to do when something goes wrong.
Lightnin Production Rentals · ThunderBank 270 kWh BESS
Revision 1 · Effective 2026-06-13
Section 1

Overview & Specs

The ThunderBank is a mobile lithium battery energy storage system housed in a truck box. It stores energy from multiple charge sources (3‑phase shore, single-phase trickle, truck alternator, rooftop solar, and ThunderBolt export) and delivers up to 90 kVA of 208 V 3‑phase AC power to the fleet. The ThunderBank can carry a production and dramatically reduce or eliminate Basecamp Generator (BG) runtime by harnessing excess solar from ThunderBolt Solar Trailers and rapid recharging.

For Cabling and Operation, Follow Industry Safety Guidelines.

Quick facts

Capacity
270 kWh total
243 kWh usable (90% DoD)
Battery chemistry
LiFePO4
Inverters
90 kVA
72 kW max continuous (24 kW/leg)
Output current
250 A/leg · 750 A total
200 A/leg continuous · 600 A total
DC bus
48 V nominal
AC output
208 / 120 V 3‑phase
Rooftop solar
~2,900 W
3‑phase AC input
30–275 A/leg, 208 V
controlled by orange dial
Max battery charge
168 A/phase · ~60.5 kW
excluding trickle charger
EV charging
Grizzl-E Ultimate 80 A Level 2
stowed in front-right jockey box
Component certs
UL 1741 · UL 1973 · UL 9540A*
* or equivalent — IEC 62619/62620 · UN 38.3
Battery range
100% → 11%
shutdown 10% · inverting resumes at 12%
Leg balance
Legs don't have to be balanced
each must stay within 24 kW continuous
Section 2

Components & where to find them

A walk-around reference. Memorize these locations before show start — the EAP and the laminated cards depend on you being able to find each item without searching.

ComponentLocation
EMERGENCY STOP button Exterior, rear-right corner of the truck box, right of the AC Output panel. Red/white decal, latches when pressed.
Control panel (screen, orange dial, 3-position switch) Exterior, rear-right corner of the truck box, in the unlocked grey Polycase. Primary operator interface — live SOC, power flow, alarms, and all daily operating controls.
AC Output panel "Waterfall" panel, right side of the rear wall (exterior). Camlocks G/W/R/Bl/Bk.
AC Input panel Exterior, front-right of truck box, labeled "Input Only". 3‑phase camlocks vertical; single-phase camlocks horizontal, directly below the 3‑phase set.
External PV breakers Exterior, shielded breaker box at the rear-left corner of the truck box, near the ABC extinguisher. Three breakers for additional solar panel inputs (customer-added or Lightnin-supplied panels). Onboard rooftop solar is also isolatable via internal breakers, but those are not field-accessible.
Alternator switch In the truck cab, left of the steering wheel. Engine-driven DC charging source. Leave the switch in the ON position unless the fault light illuminates.
Level 2 EV charger Stored in a black jockey box on the front-right of the truck box (Grizzl-E Ultimate 80 A). Customer deploys to charge EVs from the bank's AC output.
ABC fire extinguisher Mounted on the bumper at the rear-left of the truck.
Personnel door Combination-locked. Driver does not have the combo — intended for maintenance or emergency only. Combo is held by Lightnin and can be given over the phone.
Section 3

The Control Panel

The control panel sits in the unlocked grey Polycase at the rear-right corner of the truck box. It has three things you need to know: the Main Control Screen, the orange dial, and the 3-position switch. Almost every operational decision flows through this panel.

The 3-position switch

The switch sits at three clock positions: 10 o'clock = Off, 12 o'clock = Charge, 2 o'clock = On. Move the switch slowly — pause ~3 seconds at Charge when transitioning between Off and On. Slow movement lets the inverters settle and avoids fault states.

10 o'clock
Off
  • Main inverters off
  • AC output and input dead
  • EV off
  • Trickle charger still works
12 o'clock
Charge
  • Pause position — move switch slowly through here
  • Treat AC output as live
  • If no AC outputs are plugged in, this is the most efficient charging position
  • 3‑phase and trickle charging live
2 o'clock
On
  • AC output live
  • 3‑phase and trickle charging live
  • EV charger enabled
  • ThunderBolts can export power
Air conditioning and trickle charger are always on. Both are wired in a way that keeps them active in every switch position — only the EMERGENCY STOP takes them down. The air conditioning can still use the battery in the Off position; this is rarely a concern given the bank's size, but plan accordingly for weeks-long idle periods or units sitting at low SOC.
At 160°F panel temperature, the ThunderBank automatically triggers EMERGENCY STOP. The 150°F VRM alert is the warning threshold; 160°F is the auto-shutdown threshold. See the Troubleshooting section for the 150°F response procedure.
When ThunderBolts are exporting to the bank, set them to On / No Export or Off (or unplug them) before moving the ThunderBank 3-position switch. Skipping this trips an overcurrent alarm on the inverters, requiring a reset cycle to clear.

The orange dial

The orange dial does three related jobs, each shown as one of the three fields on the dial face. Push the dial to wake the display, then tap a field to bring up its setter, change the value, and tap SET to confirm (or CANCEL to back out without changing it).

Orange dial home view showing Charge Rates 60A/15A and Inverter Output Voltage 120V
Home view. Top row: 3‑phase charge rate (left, labeled 3P) and trickle charge rate (right, labeled 1P). Bottom: Inverter Output Voltage. The values shown here (60 A / 15 A / 120 V) are the post-power-loss defaults.
Fast Charge Rate setter at 60 amps
3P tap → Fast Charge Rate. Spin to set per-leg amps, then SET.
Trickle Charge Rate setter at 15 amps
1P tap → Trickle Charge Rate. Sets both trickle legs at once.
Inverter Output setter at 120 volts
Voltage tap → Inverter Output. Trims all three hot legs together.
Dial auto-resets on AC power loss. After any loss of AC power, the dial behavior resets to 60 A (3‑phase) / 15 A (trickle). Ramp the 3‑phase dial up incrementally — 30–50 A per step — until your target rate is reached. Gentle ramping is easier on the equipment and reduces the chance of inverter faults.

Main Control Screen

The screen shows live SOC, power flow, and alarms, including individual leg amps, volts, and watts on the 3‑phase AC input. The screen retains a 24-hour history; for any longer date range, use the VRM app or VRM portal. In VRM, the Dashboard covers basic information and the Advanced tab provides in-depth analysis.

Four tabs across the top — Main, Loads, Details, Alarms — switch between views. The active tab turns green. The two indicators in the upper-right (WARN and ERROR) light up when the system raises an alarm; tap Alarms to see what tripped.

Main tab showing SOC and aggregate power flow
Main — the at-a-glance view. Battery SOC, then five aggregate rows: Power Input (3‑phase shore draw), Power Output (AC loads), Solar Input, Charge Rate (net into the battery), and ESS Input. WiFi / Mqtt Status at the lower-left confirm the unit is talking to VRM; system time bottom-right updates every 30 s.
Loads tab showing per-leg AC output and 6-hour current chart
Loads — per-leg AC output, live and recent. The three header rows show current draw on Line 1, Line 2, and Line 3 in A / W / V. The chart underneath plots each leg's amps over the last ~6 hours — useful for spotting leg imbalance or load spikes against a calm baseline.
Details tab with full per-leg breakdown of input, output, solar, and ESS
Details — the full diagnostic view. Top half: per-leg Power Output and Power Input (V / A / W on L1, L2, L3). Bottom half: four Solar Input strings, the current Charge Rate, and per-leg ESS Input from any ThunderBolts. Battery temperature is shown top-right.
Alarms tab listing active alarms with WARN, ERROR, and ACK badges
Alarms — what's currently wrong. Each row is an active alarm with a status badge: ERROR (red — needs attention now), WARN (yellow — watch it), or ACK (acknowledged but unresolved). Cross-reference these with the Troubleshooting section before calling Lightnin.

The blue dot in the lower-left corner of the screen resets the display if there are any glitches or malfunctions. Resetting the screen does not affect power input or output in any way — only the display restarts.

Remote monitoring — VRM app and portal

Every ThunderBank reports live to Victron Remote Management (VRM). You can monitor the same data the on-board control screen shows, plus full historical logs, from anywhere with an internet connection.

Getting access to VRM: Call Lightnin and we’ll add you to your unit. You have two options: On a phone or tablet, install the VRM: Victron Remote Management app from the App Store or Google Play; on a computer, sign in at vrm.victronenergy.com.
Lightnin Portal (separate from VRM): portal.lightnin.com hosts our in-house tools — VRM data views, sustainability reporting, and remote control capability for units. Access is granted separately from VRM; contact Lightnin if you need it.
VRM: Victron Remote Management on the App Store
Install this app — VRM: Victron Remote Management by Victron Energy. The icon and name shown here are the only correct match; other Victron apps in the store are for different products and will not connect to your bank.

Reading the dashboard

After signing in, tap your unit (for example, B493) to open its dashboard. The view mirrors the on-board control screen: state of charge, shore draw, PV input, AC loads, and per-leg power on the 3‑phase side.

VRM dashboard for unit B493
Realtime = live data. Anything else means the feed is stale
Tap the blue icon bottom-left to switch to another unit you have access to
Per‑leg watts and frequency for L1 / L2 / L3
Tap anywhere on the screen to bring up the bottom menu bar
Advanced is the most useful tab — covered below
Dashboard view for B493. The bottom navigation bar appears when you tap the screen. Dashboard is this live view, Console is the remote control panel, Advanced opens the full historical data browser, and More contains settings and unit info.
Tip: If a number on the dashboard ever looks off, check that the status reads Realtime. If it reads anything else, the connection is slow and the data is stale. When the data is stale, use the on-board control screen as authoritative — it operates regardless of cell signal.

Scroll down the dashboard for sensors and quick history

The dashboard view is longer than the screen. Scroll down and you’ll find on-board sensor readings and a quick historical chart — useful for at-a-glance answers without opening the Advanced tab.

Temperature sensors panel
On-board temperature sensors. Interior, output breaker, input breaker, plus humidity, barometric pressure, and outside weather. Tap any tile to expand for last-24h min/max.
Installation data chart
Installation data chart. Stacked bars show consumption (red), solar (orange), and battery SOC (blue line). Tap a bar to see exact kWh and battery min/max for that hour.
Source selector dropdown
Source selector. The dropdown at the top of the chart switches between System overview, Consumption, Solar, and Shore — same chart, different signal.
Date range picker
Date range picker. Tap the date label to jump to Last 2 days, Last 7 days, Last 30 days, etc., or set a custom range.
Dashboard vs. Advanced: The dashboard charts are the fastest way to answer “how did yesterday look?” The Advanced tab (next subsection) is where the per-leg, per-MPPT, high-resolution data lives.

The Advanced tab — where the real data lives

The dashboard only shows the current moment. The Advanced tab is where you can go back in time and see exactly what each leg, each MPPT, and the battery were doing across any date range you choose.

Site selection

Section 4

Operation and Microgrid

This section covers how to use the ThunderBank to operate the loads of your basecamp and the unique interaction with ThunderBolt trailers to form a microgrid. The ThunderBolts will increase the runtime of the ThunderBank by exporting excess solar power to charge the bank or offset loads.

For Cabling and Operation, Follow Industry Safety Guidelines.

ThunderBank — Turning ON

  1. 3-position switch slowly to On — pause at Charge for ~3 seconds
  2. Verify AC Output live and stay within limits (24 kW/leg)

Load shedding — managing the fleet when walking away

Before leaving the bank to run unattended overnight, over a weekend, or during any extended idle:

  1. Leave the ThunderBank On.
  2. Keep ThunderBolts in On/Export — excess power helps the ThunderBank run longer.
  3. For units that are still needed, load-shed nonessentials — especially air conditioners on customer loads.
  4. Turn off or unplug non-ThunderBolt units that aren't needed.

Idle ThunderBolts: If a ThunderBolt isn't planning to be used, leave it in On/Export and shed its loads — it can still provide power to the ThunderBank or other units.

No-solar conditions: If solar will be 0 (overnight, indoors, snow-covered panels), ThunderBolts can be turned off too — there likely won't be enough power to export.

In normal operation, also pay careful consideration to load shedding. The same principle from "a penny saved is a penny earned" applies — every watt saved can be spent later, extending time before a recharge is needed.

ThunderBank — Turning OFF (Moving Locations or Long Term Storage)

When turning the ThunderBank Off for any reason, move ThunderBolts to On / No Export or Off first.
  1. Unplug or turn off exporting ThunderBolts first — set to On/No Export or Off, or unplug
  2. 3-position switch slowly through Charge (pause ~3 s) to Off

Single Cable System

Basecamp cabling and setup can be done the same way it's always been done. ThunderBolts and solar trailers can be placed anywhere in the basecamp cabling package.

The intent is for your ThunderBolt trailers to be operated in On/Export when cabled to the ThunderBank. In this condition, the ThunderBolts will send excess solar energy to the ThunderBank on the same cable they may receive power from. This is done automatically and without any interruption in power. The diagram below shows a sample setup and what the ThunderBank might see.

−3,000 W +1,000 W −2,000 W +2,000 W −500 W +2,000 W +3,500 W Fleet → ThunderBank ThunderBank → Fleet
Sample basecamp with 5 ThunderBolts and one ThunderBank. Yellow = excess solar flowing to ThunderBank; purple = ThunderBank supplying a draw. Labels show example net flow on each leg (+ exporting, − drawing).

Connecting ThunderBolts

ThunderBolts have a 3-position switch located by the ThunderBolt Charge Plug:

10 o'clock
Off
  • ThunderBolt off
  • No export
  • Solar charging still live
12 o'clock
On / No Export
  • Required when cabling directly to grid or generator
  • ThunderBolt powered on
  • Won't export
2 o'clock
On / Export
  • Default for ThunderBank operation
  • ThunderBolt powered on
  • Exports automatically when above Min Battery SOC

If connected to a ThunderBank, leave ThunderBolts in On / Export — they export power automatically when above Min Battery SOC. When cabling ThunderBolts directly to grid or generator power, they must be in On / No Export. ThunderBolts temporarily stop exporting while the ThunderBank has another 3‑phase charge source, and will resume automatically.

Best practice: bring ThunderBolts online one at a time. Move ThunderBolts to On / Export one at a time so each unit's safety checks happen at slightly different moments, even if only seconds apart. One way to accomplish this: leave ThunderBolts in On / No Export while you run cables to the ThunderBank, then move switches to On / Export one by one. When turning the ThunderBank Off for any reason, move ThunderBolts to On / No Export or Off first.

Detailed behavior:

VRM screenshot of TS663 ThunderBolt exporting to bank
Shore −1049 W
negative = exporting
ThunderBolt battery
idle at 100%
Local AC load
268 W
Solar producing
1508 W
ThunderBolt TS663 exporting to the bank. The negative shore number is the verification signal — this ThunderBolt is exporting through the shore line, not receiving from it.
Section 5

Charging Operations

This section describes how to charge the ThunderBank with 3‑phase or single-phase power, and includes charge rate tables for planning fill time.

Key principle. 3‑phase charging disables ThunderBolt export and runs the ThunderBolts independently. Do not leave a 3‑phase power source plugged in (or with live voltage) from a generator or shore power — 3‑phase is only meant for active recharging periods. Single-phase trickle chargers, by contrast, can be left plugged in at any time.
The orange dial sets your charge rate. It resets to a safe minimum — 60 A for 3‑phase and 10 A for single-phase — each time. You must turn the dial up to your selected charge rate, choosing a setting that is safe for the cable and power source you are using.

Switch positions — what charges in each

Charging behavior depends on the 3-position switch. 3‑phase charging is only available in the On or Charge positions; single-phase (trickle) charging works in any switch position, including Off. The cards below summarize what each position does while charging.

10 o'clock
Off
  • No 3‑phase charging
  • Single-phase trickle charging still works
  • AC output dead
12 o'clock
Charge
  • Charge-Only state — most users treat this as Pause
  • 3‑phase and trickle charging live
  • Provides pass-through power to anything plugged into the AC Outputs
  • Treat the AC Output panel as HOT
  • Most efficient charging position when nothing is plugged into AC Outputs
2 o'clock
On
  • AC output live
  • 3‑phase and trickle charging live
  • All loads run; charging occurs at the Orange Dial rate
  • If charge rate < load, the battery still discharges to meet the load

The Charge position puts the inverters into a Charge-Only state. Most users will reach for it as a Pause, but it does more than pause: it still allows 3‑phase charging, and if anything is plugged into the AC Outputs it will supply pass-through power to those loads. That is why the AC Output panel must still be treated as HOT in the Charge position.

In Charge, load must stay under the charge rate. Because the inverters are in a Charge-Only state, if the load ever exceeds the charge rate set on the orange dial, the unit will stop supplying loads for insufficient power. Set the dial above any pass-through load you expect to draw.
Charge is the most efficient position for charging when nothing is plugged into the AC Outputs. With no loads, the inverters consume no power and the batteries will not deplete if the unit is left in this position.

In the On position, all loads run and charging occurs at the rate selected on the orange dial. If the charge rate is less than your load, the battery will still discharge to meet the load — choose a dial setting above your running load if you want net charging while the unit is On.

Connecting 3‑phase shore power

  1. Connect 208 V 3‑phase shore power at the AC Input panel (front-right, "Input Only"). 3‑phase camlocks are mounted vertically. Match colors: Green / White / Red / Blue / Black. Cables can be connected in any switch position, but charging will only work in On or Charge.
  2. Move the 3-position switch slowly to On (charging while running AC output loads) or Charge (charging with no AC output loads — most efficient). Pause ~3 seconds at Charge when transitioning between Off and On to let the inverters settle.
  3. Verify on the exterior display or VRM that AC Input current is rising.
  4. Confirm the orange dial is at the auto-reset baseline (60 A for 3‑phase) and ramp up incrementally — 30–50 A per step — to your target rate (up to 275 A/leg). Use the Charge Time calculator in the Lightnin Portal to plan how long the fill will take.
  5. At 95% SOC, charging is complete. Turn off any generator to avoid wasting fuel, and unplug the 3‑phase charge source so ThunderBolts begin exporting again. Do not leave the unit plugged into a 3‑phase charge source after charging completes — 3‑phase shore presence disables ThunderBolt export, so you would lose the solar contribution from the fleet. Once disconnected, ThunderBolts resume exporting automatically. The Charge Time calculator gives the estimated fill time — or quick math: (100 × kW) ÷ 270 = Charge % per hour.

Quick reference — charge rate vs. fill time with and without load

The table below shows fill time (industry-standard 20% → 100% SOC = 216 kWh) at each dial position, for four different load scenarios.

Net battery charging = AC input − AC output load

The maximum power the batteries can charge with is 60.5 kW.

Dial
(A/leg)
AC In
(kW)
Fill time
no load
Fill time
+ 10 kW load
Fill time
+ 20 kW load
Fill time
+ 30 kW load
75 A/leg · 225 A total27.08 hr12 hr 42 min30 hr 51 mindischarging
100 A/leg · 300 A total36.06 hr8 hr 18 min13 hr 30 min36 hr
125 A/leg · 375 A total45.04 hr 48 min6 hr 10 min8 hr 38 min14 hr 24 min
150 A/leg · 450 A total54.04 hr4 hr 55 min6 hr 21 min9 hr
168 A/leg · 504 A total60.53 hr 34 min4 hr 17 min5 hr 20 min7 hr 5 min
200 A/leg · 600 A total72.03 hr 34 min3 hr 34 min4 hr 9 min5 hr 9 min
225 A/leg · 675 A total81.03 hr 34 min3 hr 34 min3 hr 34 min4 hr 14 min
250 A/leg · 750 A total90.13 hr 34 min3 hr 34 min3 hr 34 min3 hr 36 min
275 A/leg · 825 A total99.03 hr 34 min3 hr 34 min3 hr 34 min3 hr 34 min

The 168 A/leg row is where the bank starts capping battery charging at 60.5 kW (its DC ceiling). At 200 and 275 A/leg the surplus AC capacity stays available to absorb concurrent loads — which is why those rows show the same fill time as long as the load fits in the surplus. At lower dial settings combined with significant loads, the bank breaks even or actively discharges; plan the dial around your expected load. For other start/end SOC ranges or load profiles, use the Charge Time and Runtime calculators in the Lightnin Portal.

VRM screenshot of B493 charging from 3‑phase shore
Always check — if not Realtime, data is stale; use the control-panel screen for live data
Drawing from shore
41.29 kW
~120 A/leg
Battery accepting
36.16 kW @ 66%
Small AC load
1.3 kW
Rooftop solar
223 W
B493 charging from 3‑phase shore. Matches the 100 A/leg row of the table above (with a small concurrent load). For the math formula above, the kW value to use is the 36.16 kW Battery accepting number — the net charge at the battery, not the 41.29 kW the shore is delivering.
3‑phase charging only begins below 85% SOC and the bank auto-ignores the input at 95% SOC. If you plug in above 85%, the bank may refuse to charge until SOC drifts down.
Charging behavior between 88–100%. Batteries sometimes charge at unexpected rates between 88–100%. The batteries are still accepting charge, even if the percentage moves slower or faster than expected. At the upper end of charging, the voltage may rise quicker than the battery percentage. Don't be alarmed — this is normal and the batteries are working properly.

Connecting single-phase trickle chargers

Trickle chargers charge the bank regardless of the 3-position switch position, including Off. Each trickle charger needs its own single-phase hot leg; ground and neutral are always required on every trickle connection.

Trickle input is flexible and works with 120 V or 240 V, so you can use anything from a standard wall socket to a 50 A RV output.

Using a Basecamp Generator (BG) to charge

Running 3‑phase and trickle chargers at the same time

The 3‑phase shore and single-phase trickle chargers can run simultaneously. The trickle charger's power source can be the same as the 3‑phase source or completely different. Some examples:

This flexibility lets you put together a charging setup based on what power is available at the site.

Which charge path does what

SourceBehavior
3‑phase shore (208 V) Fastest path. Up to 275 A/leg AC in / 168 A per phase DC into the bank. Auto-ignores input at 95% SOC. Only begins below 85% SOC. Disables ThunderBolt export while running.
Single-phase trickle (1 or 2 chargers) ~3.4 kW DC per charger. Works in any switch position, including Off. Does NOT disable ThunderBolt export.
Truck engine alternator DC charging while the truck engine is running. Switch is in the cab, left of the steering wheel. Leave the switch in the ON position unless the fault light illuminates.
Rooftop solar (~2,900 W) Continuous in daylight. Adds to whatever else is charging. Onboard MPPT (Victron 450/200) handles regulation automatically.
ThunderBolt export Auto-starts once switch is in On and any AC charge source is removed. Disabled during 3‑phase charging.

Cabling and charge rate

(100 × kW) ÷ 270 = Charge % per hour
Easy math to estimate how long the battery has left or how long until it is full. Same formula works for discharge — just use a negative kW.
Use the net charge/discharge rate at the battery — not the AC input or AC load. On the screen this is the “Charging” or “Discharging” kW value, not the Grid or AC Loads number.
When the bank is connected to a charging source, the AC output load is primary. Load is served first, and whatever AC input is left over flows into the batteries. The batteries can absorb up to 168 A per phase (~60.5 kW DC); any input beyond load + 168 A simply isn't drawn from the charging source. So if you want to charge at max AND run loads simultaneously, set the orange dial high enough to cover the load plus 168 A/leg of charging headroom.
VRM screenshot of B490 with heavy load and limited charge
Drawing from shore
68.76 kW
~190 A/leg
Net into batteries
4.15 kW @ 90%
PV Inverter
0 W (ThunderBolts idle)
Fleet AC load
65.58 kW
Rooftop solar
2.03 kW
What happens when the dial is set too low for the load. 190 A/leg only delivers 68.8 kW, and the 65.6 kW of fleet load consumes nearly all of it — only 4 kW makes it into the batteries. To keep batteries charging at the full 60.5 kW DC ceiling while carrying this load, the dial would need to be set higher.
Section 6

Other Capabilities

Level 2 EV charging

EV charging is a large load and will significantly reduce ThunderBank runtime. A Level 2 charge can pull 8 – 19 kW depending on the vehicle — that is a substantial draw on the bank. Coordinate with the production and prioritize what matters: EV charging can usually be done elsewhere (an off-set EV charger, a public charger, the EV's home charger), while many production loads cannot.

For Cabling and Operation, Follow Industry Safety Guidelines.

Monitoring

Air conditioning

Solar contribution

Rooftop solar runs continuously in daylight. Additional solar panels can be connected to the external PV breakers located near the fire extinguisher. You must have the breakers in the OFF position before connecting or disconnecting cables to solar panels. Solar offsets load and charges the bank; you do not need to do anything to "use" it — it just contributes automatically.

The main solar contribution comes from the fleet of ThunderBolt Solar Trailers feeding the ThunderBank, which together form a microgrid. Long run times are only possible when there is additional energy flowing into the ThunderBank — from the ThunderBolts or from a solar farm on the external PV breakers.

VRM screenshot of B493 supplying loads while ThunderBolts feed power back
No grid power
(off-shore)
Battery discharging
only 6.4 kW @ 71%
ThunderBolts feeding in
5,262 W
via PV Inverter
Fleet AC load
10.52 kW
The microgrid in action. ThunderBolts are feeding ~5.3 kW back to the bank, so the bank only has to discharge ~6.4 kW to cover the 10.5 kW of load. Without the ThunderBolt support the bank would be discharging at over 10 kW.

Connecting additional solar panels

Up to three additional PV strings can be connected through the external PV breakers (shielded box at the rear-left corner, near the ABC extinguisher).

Truck alternator

Section 7

Pack-Up & Shutdown

Set ThunderBolts to On/No Export or Off before moving the ThunderBank switch. Turning the ThunderBank Off while ThunderBolts are still in Export will trip an overcurrent alarm on the inverters and force a reset cycle to clear.
  1. Set ThunderBolts to On / No Export or Off (or unplug them).
  2. Move the ThunderBank 3-position switch slowly to Off — pause at Charge for ~3 seconds to let the inverters settle.
  3. Disconnect everything from the unit:
    • AC output camlocks at the rear wall ("waterfall" panel)
    • ThunderBolt feeds
    • 3‑phase shore at the AC Input panel
    • Single-phase trickle chargers
    • Additional solar; confirm the three external PV breakers are OFF
  4. Stow all camlocks; secure cable bundles for transport.
  5. Stow the Level 2 EV charger in the black jockey box on the front-right.
Section 8

Troubleshooting

Overcurrent while turning the ThunderBank Off

The most common cause of an overcurrent alarm is turning the ThunderBank Off while ThunderBolts are still in Export — this is not recommended, because repeated alarms cause unnecessary wear and risk damage to the equipment.

Best practice: set ThunderBolts to On / No Export or Off first, then move the ThunderBank switch.

If the alarm does fire, a reset cycle is the recommended resolution:

  1. Confirm ThunderBolt export has stopped (set to On/No Export, Off, or unplug).
  2. Cycle the 3-position switch Off → On → Off, then move it to your desired state.

Overcurrent or inverter fault at any other time

Do not reset — call Lightnin. A blind reset can mask a real problem. Investigate first: read the alarm description on the Alarms tab (4th blue tab at the top of the screen), check shore cable seating, polarity, and color order, then call Lightnin if the cause isn't obvious.

Common real causes Victron may be reacting to:

Victron's fault logic: disconnect → wait ~30 seconds → retry 3–5 times → then either disconnect from the fault source for 30 minutes or ignore the AC inputs entirely.

ThunderBolt should be exporting but isn't

  1. Confirm the ThunderBank switch is in On and no 3‑phase shore is active (3‑phase blocks export).
  2. Confirm the ThunderBolt switch is in On / Export.
  3. If conditions look right for export, unplug the ThunderBolt and plug it back in to restart the ThunderBolt's safety checks.
  4. If the ThunderBolt still does not export after that, call Lightnin to diagnose.

ThunderBolt is exporting and shouldn't be

Move the ThunderBolt switch to On / No Export or unplug it.

Note: ThunderBolts in On / No Export may routinely draw a small amount of watts and briefly (less than a second) show readings of −50 W to 0 W. This is part of a "handshake" between the trailer and the power source and won't cause any harm. The setpoint is below what utility companies define as backfeed.

Screen glitches on the control panel

If the control-panel screen freezes, shows artifacts, or otherwise misbehaves, there is a small blue dot in the lower-left corner of the display. Press it to reset the screen. Resetting the screen does not affect the inverters or the bank — it only restarts the display.

If the blue dot is not visible, there are two thumb screws on the control panel. Unscrew them to allow the control panel door to swing open. Unplug the cable that goes into the back of the screen, and plug it back in.

Any glitches to the screen don't affect operation of the ThunderBank — this is a reference screen only. Loads and charging will continue to function. VRM is the primary overview tool.

Air conditioning struggling (compartment 100–120°F)

Not a fire indicator. Likely a refrigerant or compressor issue. Call Lightnin to coordinate service. The 150°F early-fire alert threshold is well above this range — you have time.

Control screen is throttling or showing partial data

Confirm EMERGENCY STOP hasn't been pressed. Use VRM as the primary reference guide.

Sensor not reporting in VRM

The temperature sensors have user-replaceable batteries. If a sensor drops off VRM, its battery has died. Call Lightnin to coordinate replacement.

When to call Lightnin vs. just continue

Section 9

Maintenance & Inspection

6-month bolt re-torque

Lightnin handles the 6-month bolt re-torque internally. Loose connections are the most common preventable cause of electrical fires; the re-torque catches them before they become a problem. If the inspection comes due during a rental, call Lightnin to schedule a good time for a tech to come out and perform the maintenance.

ABC fire extinguisher inspection

Battery Depth of Discharge

Pre-show checklist (quick version)

Post-show checklist (quick version)

Appendix

Quick Reference

A. Specs sheet

Capacity270 kWh total / 243 kWh usable
Battery chemistryLiFePO4
Inverters90 kVA
72 kW max continuous (24 kW/leg)
AC output current250 A/leg peak (750 A total)
200 A/leg continuous (600 A total)
DC bus nominal48 V
AC output208 / 120 V 3‑phase, 90 kVA
3‑phase AC input range30 – 275 A/leg (sometimes 55 A minimum)
Max battery charge current168 A/phase (AC input above 168 A flows through to AC loads)
Trickle charger contribution~3.4 kW per charger, ~6.7 kW combined (2 chargers); set 10 – 50 A with the orange dial (both legs)
Rooftop solar~2,900 W
Additional solar inputs3 external PV breakers; 4 – 10 panels per string
EV chargerGrizzl-E Ultimate 80 A Level 2
Air conditioning setpoint80°F (sensors ±5°F)
Early-fire alert threshold150°F panel sensor
Operating SOC range100% → 11% (auto-shutdown at 10%)
3‑phase charging windowAvailable below 85% SOC, auto-ignores input at 95%
Recommended cable for max charge2/0 or 4/0

B. Portal tools

C. Cross-reference

ThunderBank Operation Manual · Revision 1 · Effective 2026-06-13 · Lightnin Production Rentals