Leave voicemail or text if no immediate response. Numbers listed in priority order.
Read alongside: the ThunderBank Emergency Action Plan and the two laminated
quick-reference cards (Production Crew + Fire Department). This manual covers normal operation; the EAP
covers what to do when something goes wrong.
The ThunderBank is a mobile lithium battery energy storage system housed in a truck box. It stores
energy from multiple charge sources (3‑phase shore, single-phase trickle, truck alternator, rooftop solar,
and ThunderBolt export) and delivers up to 90 kVA of 208 V 3‑phase AC power to the
fleet. The ThunderBank can carry a production and dramatically reduce or eliminate Basecamp Generator
(BG) runtime by harnessing excess solar from ThunderBolt Solar Trailers and rapid recharging.
For Cabling and Operation, Follow Industry Safety Guidelines.
Quick facts
Capacity
270 kWh total 243 kWh usable (90% DoD)
Battery chemistry
LiFePO4
Inverters
90 kVA 72 kW max continuous (24 kW/leg)
Output current
250 A/leg · 750 A total 200 A/leg continuous · 600 A total
DC bus
48 V nominal
AC output
208 / 120 V 3‑phase
Rooftop solar
~2,900 W
3‑phase AC input
30–275 A/leg, 208 V controlled by orange dial
Max battery charge
168 A/phase · ~60.5 kW excluding trickle charger
EV charging
Grizzl-E Ultimate 80 A Level 2 stowed in front-right jockey box
Component certs
UL 1741 · UL 1973 · UL 9540A* * or equivalent — IEC 62619/62620 · UN 38.3
Battery range
100% → 11% shutdown 10% · inverting resumes at 12%
Leg balance
Legs don't have to be balanced each must stay within 24 kW continuous
Section 2
Components & where to find them
A walk-around reference. Memorize these locations before show start — the EAP and the
laminated cards depend on you being able to find each item without searching.
Component
Location
EMERGENCY STOP button
Exterior, rear-right corner of the truck box, right of the AC Output panel. Red/white decal,
latches when pressed.
Control panel (screen, orange dial, 3-position switch)
Exterior, rear-right corner of the truck box, in the unlocked grey Polycase. Primary
operator interface — live SOC, power flow, alarms, and all daily operating
controls.
AC Output panel
"Waterfall" panel, right side of the rear wall (exterior). Camlocks G/W/R/Bl/Bk.
AC Input panel
Exterior, front-right of truck box, labeled "Input Only". 3‑phase camlocks vertical;
single-phase camlocks horizontal, directly below the 3‑phase set.
External PV breakers
Exterior, shielded breaker box at the rear-left corner of the truck box, near the ABC
extinguisher. Three breakers for additional solar panel inputs (customer-added or
Lightnin-supplied panels). Onboard rooftop solar is also isolatable via internal breakers,
but those are not field-accessible.
Alternator switch
In the truck cab, left of the steering wheel. Engine-driven DC charging source. Leave the
switch in the ON position unless the fault light illuminates.
Level 2 EV charger
Stored in a black jockey box on the front-right of the truck box (Grizzl-E Ultimate 80 A).
Customer deploys to charge EVs from the bank's AC output.
ABC fire extinguisher
Mounted on the bumper at the rear-left of the truck.
Personnel door
Combination-locked. Driver does not have the combo — intended for maintenance or
emergency only. Combo is held by Lightnin and can be given over the phone.
Section 3
The Control Panel
The control panel sits in the unlocked grey Polycase at the rear-right corner of the truck box. It has
three things you need to know: the Main Control Screen, the orange dial, and the 3-position
switch. Almost every operational decision flows through this panel.
The 3-position switch
The switch sits at three clock positions: 10 o'clock = Off, 12 o'clock = Charge,
2 o'clock = On. Move the switch slowly — pause ~3 seconds at Charge when transitioning
between Off and On. Slow movement lets the inverters settle and avoids fault states.
10 o'clock
Off
Main inverters off
AC output and input dead
EV off
Trickle charger still works
12 o'clock
Charge
Pause position — move switch slowly through here
Treat AC output as live
If no AC outputs are plugged in, this is the most efficient charging position
3‑phase and trickle charging live
2 o'clock
On
AC output live
3‑phase and trickle charging live
EV charger enabled
ThunderBolts can export power
Air conditioning and trickle charger are always on. Both are wired in a way that keeps
them active in every switch position — only the EMERGENCY STOP takes them down. The air
conditioning can still use the battery in the Off position; this is rarely a concern given the bank's
size, but plan accordingly for weeks-long idle periods or units sitting at low SOC.
At 160°F panel temperature, the ThunderBank automatically triggers EMERGENCY STOP.
The 150°F VRM alert is the warning threshold; 160°F is the auto-shutdown threshold. See the
Troubleshooting section for the 150°F response procedure.
When ThunderBolts are exporting to the bank, set them to On / No Export or
Off (or unplug them) before moving the ThunderBank 3-position switch. Skipping
this trips an overcurrent alarm on the inverters, requiring a reset cycle to clear.
The orange dial
The orange dial does three related jobs, each shown as one of the three fields on the dial face.
Push the dial to wake the display, then tap a field to bring up its setter, change the value,
and tap SET to confirm (or CANCEL to back out without changing it).
Home view. Top row: 3‑phase charge rate (left, labeled 3P) and trickle
charge rate (right, labeled 1P). Bottom: Inverter Output Voltage. The values shown
here (60 A / 15 A / 120 V) are the post-power-loss defaults.
3‑phase AC input current limit (3P) — sets how much current the bank will draw per leg from
the 3‑phase shore connection. Range is 30 A to 275 A per leg. The bank may require
a minimum of 55 A under some conditions.
Trickle charger current limit (1P) — sets the per-leg AC input limit for the trickle
chargers, 10 A to 50 A. Adjusting it changes both trickle legs at the same
time; you can still plug in one leg or both as needed.
Inverter Output Voltage — trims the inverter output voltage. Useful for long AC output
cable runs where voltage drops along the cable; increasing it lifts the inverter output so the
voltage at the far end of the cable run is in the desired range. Reads line-to-neutral (~120 V)
and controls all three hot legs simultaneously.
3P tap → Fast Charge Rate. Spin to set per-leg amps, then SET.
1P tap → Trickle Charge Rate. Sets both trickle legs at once.
Voltage tap → Inverter Output. Trims all three hot legs together.
Dial auto-resets on AC power loss. After any loss of AC power, the dial behavior resets
to 60 A (3‑phase) / 15 A (trickle). Ramp the 3‑phase dial up
incrementally — 30–50 A per step — until your target rate is reached.
Gentle ramping is easier on the equipment and reduces the chance of inverter faults.
Main Control Screen
The screen shows live SOC, power flow, and alarms, including individual leg amps, volts, and
watts on the 3‑phase AC input. The screen retains a 24-hour history; for any longer
date range, use the VRM app or VRM portal. In VRM, the Dashboard covers basic information and
the Advanced tab provides in-depth analysis.
Four tabs across the top — Main, Loads, Details, Alarms —
switch between views. The active tab turns green. The two indicators in the upper-right
(WARN and ERROR) light up when the system raises an alarm; tap Alarms to see
what tripped.
Main — the at-a-glance view. Battery SOC, then five aggregate rows:
Power Input (3‑phase shore draw), Power Output (AC loads), Solar Input,
Charge Rate (net into the battery), and ESS Input. WiFi / Mqtt Status
at the lower-left confirm the unit is talking to VRM; system time bottom-right updates every
30 s.
Loads — per-leg AC output, live and recent. The three header rows show
current draw on Line 1, Line 2, and Line 3 in A / W / V.
The chart underneath plots each leg's amps over the last ~6 hours — useful for spotting
leg imbalance or load spikes against a calm baseline.
Details — the full diagnostic view. Top half: per-leg
Power Output and Power Input (V / A / W on L1, L2, L3). Bottom half: four
Solar Input strings, the current Charge Rate, and per-leg ESS Input
from any ThunderBolts. Battery temperature is shown top-right.
Alarms — what's currently wrong. Each row is an active alarm with a
status badge: ERROR (red — needs attention now), WARN (yellow — watch
it), or ACK (acknowledged but unresolved). Cross-reference these with the Troubleshooting
section before calling Lightnin.
The blue dot in the lower-left corner of the screen resets the display if there are any
glitches or malfunctions. Resetting the screen does not affect power input or output in any way
— only the display restarts.
Remote monitoring — VRM app and portal
Every ThunderBank reports live to Victron Remote Management (VRM). You can monitor the
same data the on-board control screen shows, plus full historical logs, from anywhere with
an internet connection.
Getting access to VRM: Call Lightnin and we’ll add you to your unit.
You have two options:
Use your own VRM login — create a free account at
vrm.victronenergy.com/register, tell us the email you used, and we’ll
grant that login access to your unit.
Use a temporary login from Lightnin — if you don’t want to make
your own account, we can issue you a temporary login to sign in with.
On a phone or tablet, install the VRM: Victron Remote Management app from the
App Store or Google Play; on a computer, sign in at vrm.victronenergy.com.
Lightnin Portal (separate from VRM):portal.lightnin.com hosts our
in-house tools — VRM data views, sustainability reporting, and remote control
capability for units. Access is granted separately from VRM; contact Lightnin if you
need it.
Install this app — VRM: Victron Remote Management by Victron Energy. The
icon and name shown here are the only correct match; other Victron apps in the store
are for different products and will not connect to your bank.
Reading the dashboard
After signing in, tap your unit (for example, B493) to open its dashboard. The
view mirrors the on-board control screen: state of charge, shore draw, PV input, AC loads,
and per-leg power on the 3‑phase side.
Realtime = live data. Anything else means the feed is stale →
Tap the blue icon bottom-left to switch to another unit you have access to →
← Per‑leg watts and frequency for L1 / L2 / L3
← Tap anywhere on the screen to bring up the bottom menu bar
←Advanced is the most useful tab — covered below
Dashboard view for B493. The bottom navigation bar appears when you tap the
screen. Dashboard is this live view, Console is the remote control panel,
Advanced opens the full historical data browser, and More contains
settings and unit info.
Tip: If a number on the dashboard ever looks off, check that the status
reads Realtime. If it reads anything else, the connection is slow and the data is
stale. When the data is stale, use the on-board control screen as authoritative — it
operates regardless of cell signal.
Scroll down the dashboard for sensors and quick history
The dashboard view is longer than the screen. Scroll down and you’ll find on-board
sensor readings and a quick historical chart — useful for at-a-glance answers without
opening the Advanced tab.
On-board temperature sensors. Interior, output breaker, input breaker, plus
humidity, barometric pressure, and outside weather. Tap any tile to expand for
last-24h min/max.
Installation data chart. Stacked bars show consumption (red),
solar (orange), and battery SOC (blue line). Tap a bar to see exact
kWh and battery min/max for that hour.
Source selector. The dropdown at the top of the chart switches between
System overview, Consumption, Solar, and Shore —
same chart, different signal.
Date range picker. Tap the date label to jump to Last 2 days,
Last 7 days, Last 30 days, etc., or set a custom range.
Dashboard vs. Advanced: The dashboard charts are the fastest way to
answer “how did yesterday look?” The Advanced tab (next subsection) is
where the per-leg, per-MPPT, high-resolution data lives.
The Advanced tab — where the real data lives
The dashboard only shows the current moment. The Advanced tab is where you can
go back in time and see exactly what each leg, each MPPT, and the battery were doing
across any date range you choose.
Pick a date range at the top — last 24 hours, last week, custom range, etc.
Scroll through the available widgets — AC Input (per-leg amps, volts, watts),
Battery (SOC, voltage, current, temperature), Solar (per-MPPT yield),
AC Loads, and more.
Each chart is zoom- and pan-capable. Tap a point to see the exact value and timestamp.
This is the right place to answer questions like “was one leg pulling harder than the
others last night?” or “how much solar did we actually get on day 3?”
Site selection
Coordinate parking location nearby the external power source (Basecamp Generator or grid
power) to minimize cable runs. This is the first thing to plan.
Leave enough room for access and egress around the truck box (personnel door, rear-left ABC
extinguisher, and FD vehicle access)
Confirm AHJ requirements per the EAP pre-show check list (Section B in the EAP)
Inspect that the ABC fire extinguisher tag is current and the cylinder is in place
Section 4
Operation and Microgrid
This section covers how to use the ThunderBank to operate the loads of your basecamp and the unique
interaction with ThunderBolt trailers to form a microgrid. The ThunderBolts will increase the runtime
of the ThunderBank by exporting excess solar power to charge the bank or offset loads.
For Cabling and Operation, Follow Industry Safety Guidelines.
ThunderBank — Turning ON
3-position switch slowly to On — pause at Charge for ~3 seconds
Verify AC Output live and stay within limits (24 kW/leg)
Load shedding — managing the fleet when walking away
Before leaving the bank to run unattended overnight, over a weekend, or during any extended idle:
Leave the ThunderBank On.
Keep ThunderBolts in On/Export — excess power helps the ThunderBank run longer.
For units that are still needed, load-shed nonessentials — especially air conditioners on customer loads.
Turn off or unplug non-ThunderBolt units that aren't needed.
Idle ThunderBolts: If a ThunderBolt isn't planning to be used, leave it in On/Export
and shed its loads — it can still provide power to the ThunderBank or other units.
No-solar conditions: If solar will be 0 (overnight, indoors, snow-covered panels), ThunderBolts
can be turned off too — there likely won't be enough power to export.
In normal operation, also pay careful consideration to load shedding. The same
principle from "a penny saved is a penny earned" applies — every watt saved can be spent
later, extending time before a recharge is needed.
ThunderBank — Turning OFF (Moving Locations or Long Term Storage)
When turning the ThunderBank Off for any reason, move ThunderBolts to On / No Export or Off
first.
Unplug or turn off exporting ThunderBolts first — set to On/No Export or
Off, or unplug
3-position switch slowly through Charge (pause ~3 s) to Off
Single Cable System
Basecamp cabling and setup can be done the same way it's always been done. ThunderBolts and solar
trailers can be placed anywhere in the basecamp cabling package.
The intent is for your ThunderBolt trailers to be operated in On/Export when cabled to the
ThunderBank. In this condition, the ThunderBolts will send excess solar energy to the ThunderBank on
the same cable they may receive power from. This is done automatically and without any interruption in
power. The diagram below shows a sample setup and what the ThunderBank might see.
Sample basecamp with 5 ThunderBolts and one ThunderBank. Yellow = excess solar flowing to ThunderBank;
purple = ThunderBank supplying a draw. Labels show example net flow on each leg (+ exporting, − drawing).
Connecting ThunderBolts
ThunderBolts have a 3-position switch located by the ThunderBolt Charge Plug:
10 o'clock
Off
ThunderBolt off
No export
Solar charging still live
12 o'clock
On / No Export
Required when cabling directly to grid or generator
ThunderBolt powered on
Won't export
2 o'clock
On / Export
Default for ThunderBank operation
ThunderBolt powered on
Exports automatically when above Min Battery SOC
If connected to a ThunderBank, leave ThunderBolts in On / Export — they export power
automatically when above Min Battery SOC. When cabling ThunderBolts directly to grid or generator power,
they must be in On / No Export. ThunderBolts temporarily stop exporting while the
ThunderBank has another 3‑phase charge source, and will resume automatically.
Best practice: bring ThunderBolts online one at a time. Move ThunderBolts to
On / Export one at a time so each unit's safety checks happen at slightly different moments,
even if only seconds apart. One way to accomplish this: leave ThunderBolts in On / No Export
while you run cables to the ThunderBank, then move switches to On / Export one by one.
When turning the ThunderBank Off for any reason, move ThunderBolts to On / No Export or Off
first.
Detailed behavior:
ThunderBolts take a few minutes of automatic safety checks before they begin exporting at their normal rate
Exporting appears as a negative AC Input number on the ThunderBolt's dashboard (e.g. −1049 W).
On the ThunderBank, the same power shows as PV Inverter in VRM and ESS Charging on
the Control Screen.
If a ThunderBolt should be exporting but isn't, unplug that ThunderBolt and plug it back in
to restart its safety checks. If it still does not export after that, call Lightnin to diagnose.
If a ThunderBolt is exporting and shouldn't be, move the ThunderBolt switch to On / No Export
or unplug it.
Power exported to the ThunderBank may be consumed by other loads before it reaches the bank —
in that case the energy goes to work but does not register as charge.
Safe to disconnect a ThunderBolt while it is exporting — ThunderBolts carry
anti-islanding technology that drops their output when the connection is broken.
Shore −1049 W negative = exporting →
ThunderBolt battery idle at 100%→
← Local AC load 268 W
← Solar producing 1508 W
ThunderBolt TS663 exporting to the bank. The negative shore number
is the verification signal — this ThunderBolt is exporting through the
shore line, not receiving from it.
Section 5
Charging Operations
This section describes how to charge the ThunderBank with 3‑phase or single-phase power, and
includes charge rate tables for planning fill time.
Key principle. 3‑phase charging disables ThunderBolt export and runs the
ThunderBolts independently. Do not leave a 3‑phase power source plugged in (or with live
voltage) from a generator or shore power — 3‑phase is only meant for active recharging
periods. Single-phase trickle chargers, by contrast, can be left plugged in at any time.
The orange dial sets your charge rate. It resets to a safe minimum —
60 A for 3‑phase and 10 A for single-phase — each time. You must turn the
dial up to your selected charge rate, choosing a setting that is safe for the cable and power source you are
using.
Switch positions — what charges in each
Charging behavior depends on the 3-position switch. 3‑phase charging is only available in the
On or Charge positions; single-phase (trickle) charging works in any switch position, including Off.
The cards below summarize what each position does while charging.
10 o'clock
Off
No 3‑phase charging
Single-phase trickle charging still works
AC output dead
12 o'clock
Charge
Charge-Only state — most users treat this as Pause
3‑phase and trickle charging live
Provides pass-through power to anything plugged into the AC Outputs
Treat the AC Output panel as HOT
Most efficient charging position when nothing is plugged into AC Outputs
2 o'clock
On
AC output live
3‑phase and trickle charging live
All loads run; charging occurs at the Orange Dial rate
If charge rate < load, the battery still discharges to meet the load
The Charge position puts the inverters into a Charge-Only state. Most users will reach for
it as a Pause, but it does more than pause: it still allows 3‑phase charging, and if anything is
plugged into the AC Outputs it will supply pass-through power to those loads. That is why
the AC Output panel must still be treated as HOT in the Charge position.
In Charge, load must stay under the charge rate. Because the inverters are in a Charge-Only
state, if the load ever exceeds the charge rate set on the orange dial, the unit will stop supplying
loads for insufficient power. Set the dial above any pass-through load you expect to draw.
Charge is the most efficient position for charging when nothing is plugged into the AC
Outputs. With no loads, the inverters consume no power and the batteries will not deplete if the unit is
left in this position.
In the On position, all loads run and charging occurs at the rate selected on the orange dial.
If the charge rate is less than your load, the battery will still discharge to meet the load —
choose a dial setting above your running load if you want net charging while the unit is On.
Connecting 3‑phase shore power
Connect 208 V 3‑phase shore power at the AC Input panel (front-right, "Input Only").
3‑phase camlocks are mounted vertically. Match colors: Green / White / Red / Blue / Black. Cables
can be connected in any switch position, but charging will only work in On or
Charge.
Move the 3-position switch slowly to On (charging while running AC output loads) or
Charge (charging with no AC output loads — most efficient). Pause ~3 seconds at
Charge when transitioning between Off and On to let the inverters settle.
Verify on the exterior display or VRM that AC Input current is rising.
Confirm the orange dial is at the auto-reset baseline (60 A for 3‑phase) and ramp
up incrementally — 30–50 A per step — to your target rate (up to
275 A/leg). Use the Charge Time calculator in the Lightnin Portal to plan how long the
fill will take.
At 95% SOC, charging is complete. Turn off any generator to avoid wasting fuel, and
unplug the 3‑phase charge source so ThunderBolts begin exporting again. Do not leave
the unit plugged into a 3‑phase charge source after charging completes — 3‑phase
shore presence disables ThunderBolt export, so you would lose the solar contribution from the
fleet. Once disconnected, ThunderBolts resume exporting automatically. The Charge Time calculator
gives the estimated fill time — or quick math:
(100 × kW) ÷ 270 = Charge % per hour.
Quick reference — charge rate vs. fill time with and without load
The table below shows fill time (industry-standard 20% → 100% SOC = 216 kWh) at each
dial position, for four different load scenarios.
Net battery charging = AC input − AC output load
The maximum power the batteries can charge with is 60.5 kW.
Dial (A/leg)
AC In (kW)
Fill time no load
Fill time + 10 kW load
Fill time + 20 kW load
Fill time + 30 kW load
75 A/leg · 225 A total
27.0
8 hr
12 hr 42 min
30 hr 51 min
discharging
100 A/leg · 300 A total
36.0
6 hr
8 hr 18 min
13 hr 30 min
36 hr
125 A/leg · 375 A total
45.0
4 hr 48 min
6 hr 10 min
8 hr 38 min
14 hr 24 min
150 A/leg · 450 A total
54.0
4 hr
4 hr 55 min
6 hr 21 min
9 hr
168 A/leg · 504 A total
60.5
3 hr 34 min
4 hr 17 min
5 hr 20 min
7 hr 5 min
200 A/leg · 600 A total
72.0
3 hr 34 min
3 hr 34 min
4 hr 9 min
5 hr 9 min
225 A/leg · 675 A total
81.0
3 hr 34 min
3 hr 34 min
3 hr 34 min
4 hr 14 min
250 A/leg · 750 A total
90.1
3 hr 34 min
3 hr 34 min
3 hr 34 min
3 hr 36 min
275 A/leg · 825 A total
99.0
3 hr 34 min
3 hr 34 min
3 hr 34 min
3 hr 34 min
The 168 A/leg row is where the bank starts capping battery charging at 60.5 kW (its DC ceiling).
At 200 and 275 A/leg the surplus AC capacity stays available to absorb concurrent loads —
which is why those rows show the same fill time as long as the load fits in the surplus. At lower dial
settings combined with significant loads, the bank breaks even or actively discharges; plan the dial
around your expected load. For other start/end SOC ranges or load profiles, use the Charge Time and
Runtime calculators in the Lightnin Portal.
Always check — if not Realtime, data is stale; use the control-panel screen for live data →
Drawing from shore 41.29 kW ~120 A/leg →
Battery accepting 36.16 kW @ 66% →
← Small AC load 1.3 kW
← Rooftop solar 223 W
B493 charging from 3‑phase shore. Matches the 100 A/leg row of the table
above (with a small concurrent load). For the math formula above, the kW value to
use is the 36.16 kW Battery accepting number — the net charge at
the battery, not the 41.29 kW the shore is delivering.
3‑phase charging only begins below 85% SOC and the bank auto-ignores the input at 95% SOC.
If you plug in above 85%, the bank may refuse to charge until SOC drifts down.
Charging behavior between 88–100%. Batteries sometimes charge at unexpected rates
between 88–100%. The batteries are still accepting charge, even if the percentage moves slower or
faster than expected. At the upper end of charging, the voltage may rise quicker than the battery
percentage. Don't be alarmed — this is normal and the batteries are working properly.
Connecting single-phase trickle chargers
Trickle chargers charge the bank regardless of the 3-position switch position, including Off. Each
trickle charger needs its own single-phase hot leg; ground and neutral are always required on
every trickle connection.
One hot leg — plug into Red. One trickle charger active, ~3.4 kW into the
bank
Two hot legs — plug into Red and Blue. Both trickle chargers active,
~6.7 kW combined
Single-phase camlocks are mounted horizontally on the AC Input panel, directly below the 3‑phase
set
Trickle input current is controlled with the orange dial, set between 10 – 50 A.
The dial changes both legs at the same time
Trickle input is flexible and works with 120 V or 240 V, so you can
use anything from a standard wall socket to a 50 A RV output.
Using a Basecamp Generator (BG) to charge
A BG is a valid 3‑phase source — deliver 208 V 3‑phase at your chosen input limit
Use the Charge Time calculator in the Lightnin Portal (Tools → Power → ThunderBank
Charge Time) to estimate how long the fill will take at your selected amps
Plan to shut the BG off when the bank reaches your target SOC, or when the bank auto-ignores
the input at 95%. Idling a BG past 95% wastes fuel
If you are unsure when to shut it off, the calculator will give you the fill time at your chosen
input amps
Running 3‑phase and trickle chargers at the same time
The 3‑phase shore and single-phase trickle chargers can run simultaneously. The trickle charger's
power source can be the same as the 3‑phase source or completely different. Some examples:
One BG feeding both the 3‑phase input and the trickle charger(s)
A BG running the 3‑phase input while a separate grid panel runs the trickle charger(s)
3‑phase shore from grid while the truck alternator and rooftop solar also contribute
This flexibility lets you put together a charging setup based on what power is available at the
site.
Which charge path does what
Source
Behavior
3‑phase shore (208 V)
Fastest path. Up to 275 A/leg AC in / 168 A per phase DC into the bank.
Auto-ignores input at 95% SOC. Only begins below 85% SOC. Disables ThunderBolt export while
running.
Single-phase trickle (1 or 2 chargers)
~3.4 kW DC per charger. Works in any switch position, including Off. Does NOT disable
ThunderBolt export.
Truck engine alternator
DC charging while the truck engine is running. Switch is in the cab, left of the steering
wheel. Leave the switch in the ON position unless the fault light illuminates.
Rooftop solar (~2,900 W)
Continuous in daylight. Adds to whatever else is charging. Onboard MPPT (Victron 450/200)
handles regulation automatically.
ThunderBolt export
Auto-starts once switch is in On and any AC charge source is removed. Disabled during
3‑phase charging.
Cabling and charge rate
2/0 or 4/0 cable recommended when running at the max AC input rate. For lower charge
rates and shorter runs you can size cable appropriately — pick what matches your chosen
input limit and distance
The orange dial's voltage adjust is for the AC output side (not input). On long AC output
cable runs the voltage drops across the cable; turning the dial up raises the inverter output so
the voltage at the far end of the run is in the desired range
(100 × kW) ÷ 270 = Charge % per hour
Easy math to estimate how long the battery has left or how
long until it is full. Same formula works for discharge — just use a negative kW.
Use the net charge/discharge rate at the battery — not the AC input or AC load.
On the screen this is the “Charging” or “Discharging” kW value, not the Grid
or AC Loads number.
When the bank is connected to a charging source, the AC output load is primary. Load is
served first, and whatever AC input is left over flows into the batteries. The batteries can absorb up to
168 A per phase (~60.5 kW DC); any input beyond load + 168 A simply isn't drawn from the charging source. So
if you want to charge at max AND run loads simultaneously, set the orange dial high enough to cover the
load plus 168 A/leg of charging headroom.
Drawing from shore 68.76 kW ~190 A/leg →
Net into batteries 4.15 kW @ 90% →
← PV Inverter 0 W (ThunderBolts idle)
← Fleet AC load 65.58 kW
← Rooftop solar 2.03 kW
What happens when the dial is set too low for the load. 190 A/leg
only delivers 68.8 kW, and the 65.6 kW of fleet load consumes nearly
all of it — only 4 kW makes it into the batteries. To keep batteries
charging at the full 60.5 kW DC ceiling while carrying this load, the
dial would need to be set higher.
Section 6
Other Capabilities
Level 2 EV charging
The Grizzl-E Ultimate 80 A Level 2 charger is stored in a black jockey box on the front-right
of the truck box. Customer deploys it to charge an EV from the bank's AC output
The EV itself determines the charging rate in most cases — the ThunderBank is set to
a maximum of 80 A unless the customer requests otherwise
EV charging is only enabled when the 3-position switch is in On
EV charging is a large load and will significantly reduce ThunderBank runtime. A Level 2
charge can pull 8 – 19 kW depending on the vehicle — that is a substantial draw on
the bank. Coordinate with the production and prioritize what matters: EV charging can usually be done
elsewhere (an off-set EV charger, a public charger, the EV's home charger), while many production loads
cannot.
For Cabling and Operation, Follow Industry Safety Guidelines.
Monitoring
Exterior display — the unlocked grey Polycase at the rear-right corner. Live SOC,
power flow, alarms, and per-leg amps/volts/watts. Best place for quick on-site checks
Lightnin Portal — web-based monitoring and remote controls for both the ThunderBank
and the ThunderBolt fleet. Shows the latest snapshot of readings (refreshed on demand, not
continuously streaming), plus historical data, alarm history, sustainability metrics, and the
Tools-tab calculators (Power, Charge Time, Runtime). For continuously updating values, use the
on-board screen or VRM
VRM — Victron's underlying telemetry portal. Useful for low-level diagnostics
Lightnin tech may walk you through over the phone
Air conditioning
The interior is air-conditioned to 80°F or less
The air conditioning is wired to the MultiPlus and is always on regardless of the
3-position switch — it stays running even in Off or Charge. The only thing
that takes the air conditioning down is the EMERGENCY STOP. The air conditioning can
still use the battery in the Off position; this is rarely a concern given the bank's size, but
plan accordingly for weeks-long idle periods or units sitting at low SOC
Compartment temperature sensors are reliable to ±5°F. If a sensor stops reporting
to VRM, its battery has failed — call Lightnin to coordinate replacement
100–120°F compartment temps usually mean the air conditioning is failing or
struggling, not a thermal event. Call Lightnin to diagnose
150°F+ panel temps are an early-fire alert — follow the EAP, not this manual.
Hit EMERGENCY STOP and call Lightnin. At 160°F the ThunderBank automatically triggers
EMERGENCY STOP.
Solar contribution
Rooftop solar runs continuously in daylight. Additional solar panels can be connected to the
external PV breakers located near the fire extinguisher. You must have the breakers in the OFF
position before connecting or disconnecting cables to solar panels. Solar offsets load and charges
the bank; you do not need to do anything to "use" it — it just contributes automatically.
The main solar contribution comes from the fleet of ThunderBolt Solar Trailers feeding the
ThunderBank, which together form a microgrid. Long run times are only possible when there is
additional energy flowing into the ThunderBank — from the ThunderBolts or from a solar farm on the
external PV breakers.
No grid power (off-shore) →
Battery discharging only 6.4 kW @ 71% →
← ThunderBolts feeding in 5,262 W via PV Inverter
← Fleet AC load 10.52 kW
The microgrid in action. ThunderBolts are feeding ~5.3 kW back to
the bank, so the bank only has to discharge ~6.4 kW to cover the
10.5 kW of load. Without the ThunderBolt support the bank would be
discharging at over 10 kW.
Connecting additional solar panels
Up to three additional PV strings can be connected through the external PV breakers (shielded box at
the rear-left corner, near the ABC extinguisher).
Lightnin can supply panels that can be used in strings of 4 – 10 panels per breaker
If the customer is supplying their own panels, confirm with Lightnin that the string's
short-circuit current rating is within spec before connecting
Breakers must be OFF before connecting or disconnecting panels
Once panels are connected, flip the corresponding external PV breaker to ON. Confirm on the
exterior display that solar contribution rises
Truck alternator
The alternator charges the bank while the truck engine is running. The switch is in the cab, left
of the steering wheel
Leave the switch in the ON position by default — the alternator only contributes when
the engine is running, so there's no penalty for leaving it on the rest of the time
If the switch's indicator light is illuminated, the alternator has faulted. Move the switch to
OFF and call Lightnin
Section 7
Pack-Up & Shutdown
Set ThunderBolts to On/No Export or Off before moving the ThunderBank switch. Turning
the ThunderBank Off while ThunderBolts are still in Export will trip an overcurrent alarm on the
inverters and force a reset cycle to clear.
Set ThunderBolts to On / No Export or Off (or unplug them).
Move the ThunderBank 3-position switch slowly to Off — pause at Charge for
~3 seconds to let the inverters settle.
Disconnect everything from the unit:
AC output camlocks at the rear wall ("waterfall" panel)
ThunderBolt feeds
3‑phase shore at the AC Input panel
Single-phase trickle chargers
Additional solar; confirm the three external PV breakers are OFF
Stow all camlocks; secure cable bundles for transport.
Stow the Level 2 EV charger in the black jockey box on the front-right.
Section 8
Troubleshooting
Overcurrent while turning the ThunderBank Off
The most common cause of an overcurrent alarm is turning the ThunderBank Off while ThunderBolts
are still in Export — this is not recommended, because repeated alarms cause
unnecessary wear and risk damage to the equipment.
Best practice: set ThunderBolts to On / No Export or Off first, then move the
ThunderBank switch.
If the alarm does fire, a reset cycle is the recommended resolution:
Confirm ThunderBolt export has stopped (set to On/No Export, Off, or unplug).
Cycle the 3-position switch Off → On → Off, then move it to your desired state.
Overcurrent or inverter fault at any other time
Do not reset — call Lightnin. A blind reset can mask a real problem. Investigate first:
read the alarm description on the Alarms tab (4th blue tab at the top of the screen), check shore cable
seating, polarity, and color order, then call Lightnin if the cause isn't obvious.
Common real causes Victron may be reacting to:
Too high a load on one or multiple legs
Bad voltage from a bad cable or a reversed cable
Loose camlock connection
Shore source voltage drifting out of acceptable range
Victron's fault logic: disconnect → wait ~30 seconds → retry 3–5 times → then
either disconnect from the fault source for 30 minutes or ignore the AC inputs entirely.
ThunderBolt should be exporting but isn't
Confirm the ThunderBank switch is in On and no 3‑phase shore is active (3‑phase blocks
export).
Confirm the ThunderBolt switch is in On / Export.
If conditions look right for export, unplug the ThunderBolt and plug it back in to restart
the ThunderBolt's safety checks.
If the ThunderBolt still does not export after that, call Lightnin to diagnose.
ThunderBolt is exporting and shouldn't be
Move the ThunderBolt switch to On / No Export or unplug it.
Note: ThunderBolts in On / No Export may routinely draw a small amount of watts and
briefly (less than a second) show readings of −50 W to 0 W. This is part of a
"handshake" between the trailer and the power source and won't cause any harm. The setpoint is below
what utility companies define as backfeed.
Screen glitches on the control panel
If the control-panel screen freezes, shows artifacts, or otherwise misbehaves, there is a
small blue dot in the lower-left corner of the display. Press it to reset the screen. Resetting
the screen does not affect the inverters or the bank — it only restarts the display.
If the blue dot is not visible, there are two thumb screws on the control panel. Unscrew
them to allow the control panel door to swing open. Unplug the cable that goes into the back of the
screen, and plug it back in.
Any glitches to the screen don't affect operation of the ThunderBank — this is a reference
screen only. Loads and charging will continue to function. VRM is the primary overview tool.
Air conditioning struggling (compartment 100–120°F)
Not a fire indicator. Likely a refrigerant or compressor issue. Call Lightnin to coordinate service.
The 150°F early-fire alert threshold is well above this range — you have time.
Control screen is throttling or showing partial data
Confirm EMERGENCY STOP hasn't been pressed. Use VRM as the primary reference guide.
Sensor not reporting in VRM
The temperature sensors have user-replaceable batteries. If a sensor drops off VRM, its battery has
died. Call Lightnin to coordinate replacement.
When to call Lightnin vs. just continue
Overcurrent from turning the ThunderBank Off while ThunderBolts were exporting → reset cycle
is OK (see Troubleshooting). If it persists after one cycle, call Lightnin
Any other overcurrent or inverter fault → don't reset — call Lightnin.
A blind reset can mask a real problem
Any thermal indicator (150°F panel alert, vapor, odor) → follow the EAP, not this
manual
Any alternator fault indicator → leave OFF and call Lightnin
ThunderBolt that still is not exporting after an unplug-and-replug attempt →
call Lightnin
Section 9
Maintenance & Inspection
6-month bolt re-torque
Lightnin handles the 6-month bolt re-torque internally. Loose connections are the most common
preventable cause of electrical fires; the re-torque catches them before they become a problem.
If the inspection comes due during a rental, call Lightnin to schedule a good time for a tech to
come out and perform the maintenance.
ABC fire extinguisher inspection
Inspect the tag date before every show. If the tag is past due, notify Lightnin
Confirm the cylinder is in its bracket on the bumper at the rear-left of the truck
Confirm the gauge needle is in the green band
Battery Depth of Discharge
The batteries have a 90% Depth of Discharge.
Do not plan a load profile that takes the bank below 11% — running deeper degrades cell
life over time
At 10% SOC the bank performs an automatic shutdown. Once shut down, the bank can still
accept a charge in the On or Charge switch position. Inverting (AC output) only
resumes once SOC reaches 12% or higher
Use the Runtime calculator to plan how long a given load can run before reaching the
cutoff
Pre-show checklist (quick version)
ABC extinguisher tag current, cylinder in bracket
EAP and laminated cards present and current
6-month inspection up to date (Lightnin tracks)
Point person identified to handle emergency planning per EAP Section B
Post-show checklist (quick version)
Pack-up sequence completed in order (Section 7)
All camlocks stowed, no loose cables
Level 2 EV charger stowed in jockey box
Alternator switch OFF
External PV breakers OFF
Any alarms or unusual events logged for Lightnin debrief
Appendix
Quick Reference
A. Specs sheet
Capacity
270 kWh total / 243 kWh usable
Battery chemistry
LiFePO4
Inverters
90 kVA 72 kW max continuous (24 kW/leg)
AC output current
250 A/leg peak (750 A total) 200 A/leg continuous (600 A total)
DC bus nominal
48 V
AC output
208 / 120 V 3‑phase, 90 kVA
3‑phase AC input range
30 – 275 A/leg (sometimes 55 A minimum)
Max battery charge current
168 A/phase (AC input above 168 A flows through to AC loads)
Trickle charger contribution
~3.4 kW per charger, ~6.7 kW combined (2 chargers); set 10 – 50 A with the orange dial (both legs)
Rooftop solar
~2,900 W
Additional solar inputs
3 external PV breakers; 4 – 10 panels per string
EV charger
Grizzl-E Ultimate 80 A Level 2
Air conditioning setpoint
80°F (sensors ±5°F)
Early-fire alert threshold
150°F panel sensor
Operating SOC range
100% → 11% (auto-shutdown at 10%)
3‑phase charging window
Available below 85% SOC, auto-ignores input at 95%
Recommended cable for max charge
2/0 or 4/0
B. Portal tools
Power Calculator — convert amps ↔ kW for 3‑phase or single-phase circuits.
Lightnin Portal → Tools → Power → Power Calculator.
Charge Time — estimate fill time for a given amp/kW input. Lightnin Portal →
Tools → Power → ThunderBank Charge Time.
Runtime — estimate how long the bank will run a given load (with optional solar offset
or trailer-count solar contribution). Lightnin Portal → Tools → Power → ThunderBank
Runtime.
C. Cross-reference
ThunderBank Emergency Action Plan — what to do when something goes wrong
Production Crew Emergency Card — laminated quick-ref for crew, kept near the unit
Fire Department Quick Reference Card — laminated quick-ref handed to first
responders