LiFePO4 is water-suitable. Apply copious water for cooling
— do not ration. Lower toxicity and lower runaway risk than NMC, but
SCBA mandatory (HF gas + organic vapors possible).
On-Arrival Checklist
- Confirm EMERGENCY STOP pressed (rear-right corner) and truck engine OFF. If not, press E-stop.
- Visually check camlock connections at AC In / AC Out for arcing or melting.
- Stay-back: 50 ft minimum, 100 ft if venting / flame / audible relief.
- Call Lightnin for live consult: 678-472-5682 (backup 470-244-3905, 3rd 877-433-0313). Lightnin can grant the incident commander real-time VRM data (cell temps, voltages, alarms).
Battery Thermal Event
- Apply water liberally until cell temps stabilize.
- Monitor 24-48 hr post-extinguish for reignition.
- Full structural turnout + SCBA.
- Contain runoff where practical; notify environmental authorities.
- Acceptable media (NFPA 855): water preferred (cools). Dry chem and CO2/clean-agent knock down flame but don't cool making reignition likely.
AC Panel Electrical Fire
- Built-in suppression may have activated. Confirm EMERGENCY STOP pressed.
- Treat as Class C until batteries confirmed not involved.
- Suppression activation cannot be directly confirmed. Lightnin can monitor compartment + panel temperature trends in VRM as a proxy.
Residual hazards: ~270 kWh stored at 48 VDC even after EMERGENCY STOP.
Batteries isolated but charged. Truck-box panels may be hot — use a thermal-imaging camera
before approach. Vehicle hazards remain — truck fuel, engine, tires. A truck-cab fire
can spread to the BESS in the box.